# The attack took a day; getting back on the grid has taken 62 days

> As of October 28, Chile's 103 MW Huatacondo solar plant was still offline, 62 days after the August 27 cyberattack, and its 98 MW / 312 MWh battery system, then in commissioning, had not been reconnected. In October, three CEN-coordinated companies updated their firewalls.

- Published by: EnergySage, an energy intelligence firm (Santiago, Chile)
- Date: 2026-10-30
- URL: https://energysage.cl/en/analisis/ciberataque-camino-de-vuelta/
- Spanish version: https://energysage.cl/analisis/ciberataque-camino-de-vuelta/

## In brief

- On August 27, the system operator's daily reports logged events whose reported cause was a cyberattack. Since late June, they had logged no other events with that cause.
- The 103 MW Huatacondo solar plant in Pozo Almonte has been listed at 0% availability because of that cyberattack in every daily report since, 62 days as of October 28.
- Its 98 MW / 312 MWh battery system was in its commissioning period. The attack disconnected it, and as of October 28 it remained in commissioning, with no reconnection logged.
- Between October 23 and 27, three CEN-coordinated companies updated firewalls at their substations. Since late June, the daily reports had logged no update of this kind.
- The CNE's draft cybersecurity technical regulation closed its public consultation on October 2 and has no final version yet.

Everything that follows comes from the official daily reports of the Dispatch and Control Center of the CEN, Chile's independent system operator (ISO), a public record anyone can verify.

On August 27, those reports logged events whose reported cause was a cyberattack. Since late June, they had logged no other events with that cause.

What the reports show next is the same asset, every morning. The 103 MW Huatacondo solar plant, in the municipality of Pozo Almonte in Chile's Tarapacá region, is listed at 0% availability because of the cyberattack in every daily report from August 27 to October 28. As of October 28, no return to service has been logged. That is 62 days.

Next to the plant sits the Huatacondo battery energy storage system, rated at 98 MW / 312 MWh. It was not in commercial operation: it was in commissioning, energized for testing. The attack disconnected it as well, and as of October 28 it is still in commissioning, with no reconnection logged.

On October 29, the Chilean trade outlet Recargados covered the case in a story whose headline translates as ["A cyberattack took 312 MWh of batteries offline in Chile, and two months later they are still down"](https://recargados.net/un-ciberataque-apago-312-mwh-de-baterias-en-chile-y-llevan-dos-meses-sin-volver/) and cited [our August 31 analysis](/analisis/ciberseguridad-electrica-norma-consulta-publica/). The cause is the one the company reported to the system operator. There is no public investigation into its origin or scope, and this analysis does not offer one.

## One day to get in, more than two months to come back

The attack was logged at a specific hour of a single day. The return is measured in weeks and still has no date.

Returning to service means different things for the two units. For the solar plant, it means reconnecting a plant that was operating. For the battery system, it means resuming an interrupted commissioning process. As Recargados notes, several parties have access to the systems at that stage, which lengthens the work of verifying that nothing was altered.

Recargados explains what that return requires. Re-energizing a battery system after a cyber incident means verifying that the firmware, protection settings, and control logic were not altered, and part of the testing may need to be repeated.

That account is consistent with how such a facility is built. A battery storage system is made up of several layers that communicate with one another: the cells and their battery management system, the inverter, the protection relays, the plant controller, and the link to the remote operations center (ROC). If any of those layers may have been tampered with, the question shifts from whether the equipment works to whether it does what its configuration says. Answering it requires a defined sequence, and the layer you can trust least sets the starting point. This last point is our own interpretation of how verification works: the daily reports do not say what is being reviewed or how far along it is.

## Three firewalls in five days

Between October 23 and 27, the daily reports logged three firewall updates at substations of three different CEN-coordinated companies. Each one filed an emergency outage request and closed it the same day or the next.

- **October 23:** a Fortinet device was updated in response to a "possible vulnerability to cyberattacks." The work took 46 minutes.
- **October 26:** a Fortinet device was updated in response to a "critical security vulnerability." The work took 45 minutes.
- **October 27:** a corporate firewall received a firmware update following a communications outage. The work took 3 hours and 41 minutes.

We do not name the companies or their substations: publishing which equipment protects each facility would give an attacker useful information. The records are in the system operator's daily reports for those dates.

None of the companies disclosed a vulnerability identifier, so the daily reports do not show what was fixed. The absence of a log entry does not prove such work never happened, since not every update of this kind requires an emergency outage request. What it does show is that work of this kind began to appear in the official record in October.

Separately, on October 23 the Canadian Centre for Cyber Security published [advisory AV26-1081](https://cyber.gc.ca/en/alerts-advisories/fortinet-security-advisory-av26-1081), which reported vulnerabilities in FortiOS and other Fortinet products as of October 21 and recommended updating. For FortiOS, the patched versions are 8.0.2, 7.6.8, 7.4.13, and 7.2.14. The daily reports do not say whether the updates logged in Chile were a response to that advisory.

## The regulation is still pending

The CNE (National Energy Commission), Chile's energy regulator, opened public consultation on its draft cybersecurity technical regulation on August 28, the day after the events, and extended the consultation period to October 2. As of this writing, no final version has been published. According to Recargados, the first maturity measurement is scheduled for 2028.

Until then, how long an asset takes to return to service depends on what each company has prepared, since no common requirement applies: its practices, its supplier contracts, and what it has already rehearsed.

## Two questions for every company

The first is how much each month with an asset offline costs the company. A plant stops selling its energy; a battery system stops charging in low-price hours and discharging in high-price ones; and one still in commissioning pushes back the date it starts earning revenue. The figure depends on each contract and cannot be derived from the daily reports.

The second is who, inside the organization or among its suppliers, knows the path back to service: what is checked first, what evidence goes to the system operator, which tests are repeated, and who signs off.

**Further reading**

- [Grid cybersecurity: Chile's draft regulation enters public consultation as the sector already reports attacks](/analisis/ciberseguridad-electrica-norma-consulta-publica/) (August 31, 2026)
- [Cybersecurity in energy assets: beyond regulatory compliance](/analisis/ciberseguridad-activos-energeticos-regulatorio/)
- [Designing tomorrow's Chilean power system today](/analisis/energia-con-resiliencia-chile-electrico/)

*Sources: official daily reports of the Dispatch and Control Center of the CEN, in particular those for August 27 and October 23, 26, 27, and 28, 2026; Recargados, "Un ciberataque apagó 312 MWh de baterías en Chile y llevan dos meses sin volver," October 29, 2026; Canadian Centre for Cyber Security, advisory AV26-1081, October 23, 2026; CNE (National Energy Commission), draft cybersecurity technical regulation (Norma Técnica de Ciberseguridad y Seguridad de la Información), public consultation from August 28 to October 2, 2026.*